 
A Look at Possible Changes to the 2012 Building Code Cycle
May 14, 2010
The International Code Council (ICC) hearings to complete proceedings
on development of the 2012 edition of the International Building
Code (IBC) begin tomorrow in Dallas. A number of proposals relating
to fire-rated glass and glazing will be heard. Thom Zaremba, the
Glass Association of North Americas (GANA) consultant for
the Glazing Industry Code Committee Fire/Structural/Safety Code,
provided USGNN.com/USGlass magazine with information
on some of these key proposals.
FS4-09/10
If adopted, FS4-09/10 would add a new section, 703.4, to the IBC,
which would require all fire-resistance rated systems tested to
ASTM E 119 Standard Test Methods for Fire Tests of Building Construction
and Materials to be tested without the use of automatic sprinklers
or other fire suppression systems incorporated into the test assembly.
The Fire Safety Committee recommended adoption, but two public comments
challenging that recommendation were submitted. The first asks that
the proposal be adopted, but modified to clarify that nothing in
it is intended to limit the discretion of building code officials
under IBC sections 104.10 or 104.11. These sections allow the use
of alternate materials or methods to comply with the building code
if it can be demonstrated to the satisfaction of the building code
official that they provide equivalent performance. The second public
comment asks that the proposal be disapproved. It argues that the
proposal is aimed at overruling the use of a specific ICC ES Report,
namely, Report 2397, which approved a system using sprinklers as
an equivalent to systems using fire-resistance rated materials tested
to ASTM E 119.
FS107-09/10
FS107-09/10 re-writes significant portions of Chapter 7 of the
IBC dealing with how fire-rated glazing must be marked. Although
its provisions are too extensive to list in detail, the heart and
soul of this proposal are contained in three tables.
The first table, 715.3, is new. It correlates the various test
procedures applicable to fire-rated glazing to the designations
used to mark the glazings and to the types of assemblies where those
types of glazing assemblies may be used. There are three basic test
standards applicable to fire-rated glazing, and products tested
to each of these standards are assigned unique marks. Glazing tested
to ASTM E 119 is marked with a W. Use of that mark indicates
that the glazing meets the criteria established for a fire wall
assembly. Glazing tested to NFPA 257 is marked with an OH
which indicates that it meets the criteria established for fire
window assemblies (opening protectives), including the hose stream
test. Glazing tested to NFPA 252 can feature several possible marks.
First, it will always be marked with a D to indicate
that it meets the test criteria for fire doors. In addition, it
may be marked with an H if it passes the hose stream
test and it may also be marked with a T if it meets
a 450º F temperature rise requirement for 30 minutes. All of
the marks must include the time in minutes for which the glazing
assembly has been rated.
The other two tables addressed by this proposal are Tables 715.5
and 715.6. Both of these exist in the current code, but the proposal
modifies them to include, as to each fire-rated application, the
markings that fire-rated glazing assemblies used in those applications
must bear.
If adopted, the marking system detailed in the proposal and its
tables will make it easy for architects and specifiers to design
fire-rated construction and match the right fire-rated
glazing to the right application. It will also make
it easy for building code inspectors to determine whether the right
fire-rated glazing is being used in the right application.
E113/09-10
Also being considered is E113-09/10, which deals with fire-protection
systems required in educational occupancies (E-occupancies). Currently,
E-occupancies with fire areas less than 12,000 square feet (typically
small schools often in rural areas) are not required to include
automatic sprinkler systems, though 1-hour fire-rated exit corridors
are required. In fire areas exceeding 12,000 square feet, however,
the code does require the installation of automatic sprinklers,
but the 1-hour fire-rated exit corridor requirement is eliminated.
If adopted, E113-09/10 would require both automatic sprinklers
and 1-hour fire-rated exit corridors in E-occupancies with fire
areas greater than 12,000 square feet. There are several reasons
for this. First, there are more than 5,000 school fires in this
country every year and most of those fires break out while students
and teachers are in their classrooms. Second, in the lessons learned
from Columbine and other violent events involving schools, school
administrators have decided to backtrack from rules requiring occupants
to immediately exit school buildings when a fire alarm is sounded
out of concern that false fire alarms could be used to draw students
out of their classrooms and into the open where they could be victimized.
Instead, school systems are now moving to the use of lockdown
procedures, where students are literally locked in their classrooms
until a school official signals that the area is free of intruders
intending harm.
While these new lockdown procedures reduce the risk that students
will be victims of violence, they increase the risk that they will
become victims of fire by virtue of increasing the amount of time
that they are compelled to remain in a burning building after a
fire alarm is sounded. One effective way to mitigate this increased
risk is to add passive fire-protection systems to the active or
automatic sprinkler systems that are already required.
The ICCs code change proposals will take place May 15-23
in Dallas. Stay tuned to USGNN.com for code change proposal
updates all next week.
Need more info and analysis about the issues?
CLICK
HERE to subscribe to USGlass magazine.
|